apcaccess(8)


NAME

     apcaccess --- retrieve status information from apcupsd(8)

SYNOPSIS

     apcaccess [-f <config-file>] [-h <host>[:<port>]] [-p <parameter-name>]
           [-u] [<command>] [<host>[:<port>]]

DESCRIPTION

     apcaccess is a program which prints out the complete status of most
     American Power Conversion Corp. (APC) UPSes provided you have the
     apcupsd(8) daemon installed, properly configured and running. It can
     access status information from any APC UPS attached to the localhost or
     attached to any computer on the network which is running apcuspd in NIS
     mode.

     The command line options are:

     -f         configuration file of apcupsd (default is usually
            /etc/apcupsd/apcupsd.conf)

     -h         hostname and port of apcupsd to communicate with.  The default
            hostname and port are obtained from the configuration file.

     -p         Report only the value of the named parameter instead of all
            parameters and values.

     -u         Remove units field for easier parsing by scripts.

     <command>  An optional command, unless a hostname is also being
            specified. The only implemented command is status Shorthand
            for status localhost:3551.  This produces a full printout of
            the available status information for the associated UPS.

     <host>     An optional hostname which may be a bare machine name, fully
            qualified domain name or IP address.

     :<port>    An optional port number where a hostname argument has been
            specified. The default is 3551, the official port number
            assigned by IANA for the apcupsd NIS server.  The default
            hostname and port are obtained from the configuration file.

     apcaccess uses apcupsd's inbuilt Network Information Server (NIS) -- no
     relation to Sun's NIS/YP service -- to obtain the current status
     information from the UPS on the local or remote computer. It is therefore
     necessary to have the following configuration directives:

         NETSERVER on
         NISPORT 3551

     in the /etc/apcupsd/apcupsd.conf configuration file so that the Network
     Information Server will be accessible.  Firewall rules for appropriate
     network access may also be needed.

STATUS REPORT FORMAT

     The status report output format is simple ASCII. Generally there is a
     single piece of information on each line of output. The content varies
     based on the model of UPS being used and, in some cases, the firmware
     version.

EXAMPLES

     Set out below is a sample of the status output which may be generated for
     the specified UPS models.

   All models
     APC         : version, number of records and number of bytes following
     DATE        : Date and time of last update from UPS
     HOSTNAME    : hostname of computer running apcupsd
     VERSION     : apcupsd version number, date and operating system
     UPSNAME     : UPS name from configuration file (dumb) or EEPROM (smart)
     CABLE       : Cable type specified in the configuration file
     MODEL       : UPS model derived from UPS information
     UPSMODE     : Mode in which UPS is operating
     STARTTIME   : Date and time apcupsd was started
     STATUS      : UPS status.  One or more of the following (space-
             separated): CAL TRIM BOOST ONLINE ONBATT OVERLOAD LOWBATT
             REPLACEBATT NOBATT SLAVE SLAVEDOWN
             or
             COMMLOST
             or
             SHUTTING DOWN
     MASTERUPD   : Last time the master sent an update to the slave
     ENDAPC      : Date and time of status information was written

   Smart-UPS and Matrix-UPS (Smart Signalling)
     LINEV     : Current input line voltage
     LOADPCT   : Percentage of UPS load capacity used as estimated by UPS
     BCHARGE   : Current battery capacity charge percentage
     TIMELEFT  : Remaining runtime left on battery as estimated by the UPS
     MBATTCHG  : Min battery charge % (BCHARGE) required for system shutdown
     MINTIMEL  : Min battery runtime (MINUTES) required for system shutdown
     MAXTIME   : Max battery runtime (TIMEOUT) after which system is shutdown
     MAXLINEV  : Maximum input line voltage since apcupsd started
     MINLINEV  : Min (observed) input line voltage since apcupsd started
     OUTPUTV   : Current UPS output voltage
     SENSE     : Current UPS sensitivity setting for voltage fluctuations
     DWAKE     : Time UPS waits after power off when the power is restored
     DSHUTD    : Delay before UPS powers down after command received
     DLOWBATT  : Low battery signal sent when this much runtime remains
     LOTRANS   : Input line voltage below which UPS will switch to battery
     HITRANS   : Input line voltage above which UPS will switch to battery
     RETPCT    : Battery charge % required after power off to restore power
     ITEMP     : UPS internal temperature in degrees Celcius
     ALARMDEL  : Delay period before UPS starts sounding alarm
     BATTV     : Current battery voltage
     LINEFREQ  : Current line frequency in Hertz
     LASTXFER  : Reason for last transfer to battery since apcupsd startup
     NUMXFERS  : Number of transfers to battery since apcupsd startup
     XONBATT   : Date, time of last transfer to battery since apcupsd startup
     TONBATT   : Seconds currently on battery
     CUMONBATT : Cumulative seconds on battery since apcupsd startup
     XOFFBAT   : Date, time of last transfer off battery since apcupsd startup
     SELFTEST  : Date and time of last self test since apcupsd startup
     STESTI    : Self-test interval
     STATFLAG  : UPS status flag in hex
     DIPSW     : Current UPS DIP switch settings
     REG1      : Fault register 1 in hex
     REG2      : Fault register 2 in hex
     REG3      : Fault register 3 in hex
     MANDATE   : UPS date of manufacture
     SERIALNO  : UPS serial number
     BATTDATE  : Date battery last replaced (if set)
     NOMOUTV   : Nominal output voltage to supply when on battery power
     NOMBATTV  : Nominal battery voltage
     EXTBATTS  : Number of external batteries (for XL models)
     BADBATTS  : Number of bad external battery packs (for XL models)
     FIRMWARE  : UPS firmware version
     APCMODEL  : APC model information

   Newer Back-UPS Pro (Smart Signalling)
     LINEV     : Current input line voltage
     LOADPCT   : Percentage of UPS load capacity used
     MBATTCHG  : Min battery charge % (BCHARGE) required for system shutdown
     MINTIMEL  : Min battery runtime (MINUTES) required for system shutdown
     MAXTIME   : Max battery runtime (TIMEOUT) after which system is shutdown
     MAXLINEV  : Maximum input line voltage since apcupsd startup
     MINLINEV  : Minimum input line voltage since apcupsd startup
     OUTPUTV   : Current UPS output voltage
     BATTV     : Current battery charge voltage
     STATFLAG  : UPS status flag in hex

   Back-UPS RS 1500 (USB)
     LINEV     : Current input line voltage
     LOADPCT   : Percentage of UPS load capacity used
     BCHARGE   : Current battery capacity charge percentage
     TIMELEFT  : Remaining runtime left on battery as estimated by UPS
     MBATTCHG  : Min battery charge % (BCHARGE) required for system shutdown
     MINTIMEL  : Min battery runtime (MINUTES) required for system shutdown
     MAXTIME   : Max battery runtime (TIMEOUT) after which system is shutdown
     *OUTPUTV  : Current UPS output voltage
     *DWAKE    : Time UPS waits after power off when the power is restored
     *DSHUTD   : Delay before UPS powers down after command received
     LOTRANS   : Input line voltage below which UPS will switch to battery
     HITRANS   : Input line voltage above which UPS will switch to battery
     *RETPCT   : Battery charge % required after power off to restore power
     *ITEMP    : UPS internal temperature in degrees Celcius
     ALARMDEL  : Delay period before UPS starts sounding alarm
     BATTV     : Current battery voltage
     *LINEFREQ : Current line frequency in Hertz
     *LASTXFER : Reason for last transfer to battery since apcupsd startup
     NUMXFERS  : Number of transfers to battery since apcupsd startup
     XONBATT   : Date, time of last transfer to battery since apcupsd startup
     TONBATT   : Seconds currently on battery
     CUMONBATT : Cumulative seconds on battery since apcupsd startup
     XOFFBAT   : Date, time of last transfer off battery since apcupsd startup
     SELFTEST  : Date and time of last self test since apcupsd startup
     STATFLAG  : UPS status flag in hex
     MANDATE   : UPS date of manufacture
     SERIALNO  : UPS serial number
     BATTDATE  : Date battery last replaced (if set)
     NOMBATTV  : Nominal battery voltage
     FIRMWARE  : UPS firmware version
     APCMODEL  : APC model information
     * presence dependant on USB firmware version.

   Web/SNMP (AP9716) or PowerNet SNMP (AP9605) SmartSlot Card
     LINEV     : Current input line voltage
     LOADPCT   : Percentage of UPS load capacity used as estimated by UPS
     BCHARGE   : Current battery capacity charge percentage
     TIMELEFT  : Remaining runtime left on battery as estimated by UPS
     MBATTCHG  : Min battery charge % (BCHARGE) required for system shutdown
     MINTIMEL  : Min battery runtime (MINUTES) required for system shutdown
     MAXTIME   : Max battery runtime (TIMEOUT) after which system is shutdown
     MAXLINEV  : Maximum input line voltage since apcupsd startup
     MINLINEV  : Minimum input line voltage since apcupsd startup
     OUTPUTV   : UPS output voltage
     SENSE     : Current UPS sensitivity setting for voltage fluctuations
     DWAKE     : Time UPS waits after power off when the power is restored
     DSHUTD    : Delay before UPS powers down after command received
     DLOWBATT  : Low battery signal sent when this much runtime remains
     LOTRANS   : Input line voltage below which UPS will switch to battery
     HITRANS   : Input line voltage above which UPS will switch to battery
     RETPCT    : Battery charge % required after power off to restore power
     ITEMP     : UPS internal temperature in degrees Celcius
     ALARMDEL  : Delay period before UPS starts sounding alarm
     LINEFREQ  : Current line frequency in Hertz
     NUMXFERS  : Number of transfers to battery since apcupsd startup
     TONBATT   : Seconds currently on battery
     CUMONBATT : Cumulative seconds on battery since apcupsd startup
     XOFFBATT  : Date, time of last transfer off battery since apcupsd startup
     STESTI    : Self-test interval
     STATFLAG  : UPS status flag in hex
     DIPSW     : Current UPS DIP switch settings
     MANDATE   : UPS date of manufacture
     SERIALNO  : UPS serial number
     BATTDATE  : Date battery last replaced (if set)
     NOMOUTV   : Nominal output voltage to supply when on battery power
     NOMPOWER  : Nominal power output in watts
     EXTBATTS  : Number of external batteries (for XL models)
     BADBATTS  : Number of bad external battery packs (for XL models)
     FIRMWARE  : UPS firmware version
     APCMODEL  : APC model information

   Share-UPS (AP9270) (Basic port)
     MBATTCHG  : Min battery charge % (BCHARGE) required for system shutdown
     MINTIMEL  : Min battery runtime (MINUTES) required for system shutdown
     MAXTIME   : Max battery runtime (TIMEOUT) after which system is shutdown
     NUMXFERS  : Number of transfers to battery since apcupsd startup
     TONBATT   : Seconds currently on battery
     CUMONBATT : Cumulative seconds on battery since apcupsd startup
     XOFFBATT  : Date, time of last transfer off battery since apcupsd startup
     STATFLAG  : UPS status flag in hex

   UPS Environmental Monitoring SmartSlot Card (AP9612TH)
     HUMIDITY  : Ambient humidity
     AMBTEMP   : Ambient temperature

   Back-UPS Pro and Smart-UPS v/s (Smart Signalling)
     LINEFAIL  : Input line voltage status.
     BATTSTAT  : Battery status.
     LASTXFER  : Last (observed) transfer to battery.

   Back-UPS and Net-UPS (Simple Signalling)
     LINEFAIL  : Input line voltage status.
     BATTSTAT  : Battery status.
     STATFLAG  : UPS status flag in hex.

FILES

     /etc/apcupsd/apcupsd.conf

SEE ALSO

     apcupsd.conf(5), apcupsd(8).

     The HTML apcupsd manual installed on your system or available online at
     http://www.apcupsd.org/

AUTHORS

   This page
     Trevor Roydhouse

   Software
     Adam Kropelin (current Project Manager and Code Maintainer)
     Kern Sibbald (former Project Manager and Code Maintainer)
     Riccardo Facchetti (former Project Manager and Code Maintainer)
     Andre M. Hedrick (Project Founder and former Code Maintainer)

   Contributors
     An enormous number of users who have devoted their time and energy to
     this project -- thanks.





Opportunity


Personal Opportunity - Free software gives you access to billions of dollars of software at no cost. Use this software for your business, personal use or to develop a profitable skill. Access to source code provides access to a level of capabilities/information that companies protect though copyrights. Open source is a core component of the Internet and it is available to you. Leverage the billions of dollars in resources and capabilities to build a career, establish a business or change the world. The potential is endless for those who understand the opportunity.

Business Opportunity - Goldman Sachs, IBM and countless large corporations are leveraging open source to reduce costs, develop products and increase their bottom lines. Learn what these companies know about open source and how open source can give you the advantage.





Free Software


Free Software provides computer programs and capabilities at no cost but more importantly, it provides the freedom to run, edit, contribute to, and share the software. The importance of free software is a matter of access, not price. Software at no cost is a benefit but ownership rights to the software and source code is far more significant.


Free Office Software - The Libre Office suite provides top desktop productivity tools for free. This includes, a word processor, spreadsheet, presentation engine, drawing and flowcharting, database and math applications. Libre Office is available for Linux or Windows.





Free Books


The Free Books Library is a collection of thousands of the most popular public domain books in an online readable format. The collection includes great classical literature and more recent works where the U.S. copyright has expired. These books are yours to read and use without restrictions.


Source Code - Want to change a program or know how it works? Open Source provides the source code for its programs so that anyone can use, modify or learn how to write those programs themselves. Visit the GNU source code repositories to download the source.





Education


Study at Harvard, Stanford or MIT - Open edX provides free online courses from Harvard, MIT, Columbia, UC Berkeley and other top Universities. Hundreds of courses for almost all major subjects and course levels. Open edx also offers some paid courses and selected certifications.


Linux Manual Pages - A man or manual page is a form of software documentation found on Linux/Unix operating systems. Topics covered include computer programs (including library and system calls), formal standards and conventions, and even abstract concepts.